Mezzanines, Lofts, Attics and Basements
A-015 · R03 · Awaiting human acceptance
On this page
Lofts provide limited overhead storage space, mezzanines create intermediate floors within rooms, and attics occupy space below sloping roofs. Basements provide floors partly or wholly below ground. Goa's building regulations distinguish these spaces by their position, dimensions, permitted uses and treatment under Floor Area Ratio (FAR) calculations.
Lofts #
A loft is a residual space above normal floor level, intended for storage and without a direct staircase leading to it (Regulation 2(81)). Its projection from a habitable-room wall cannot exceed 0.75 m, while lofts over corridors, toilets, water closets and bathrooms may cover their entire area. The definition specifies a minimum 2.10 m headroom below and a maximum loft height of 1.50 m.
The total loft area cannot exceed 20% of the containing room's floor area, except that bathrooms and water closets may have lofts over their full area (Regulation 13.8(a)). That provision specifies a construction height of 2.20 m from the room floor. Editor's note: The definition's 2.10 m headroom and Regulation 13.8(a)'s 2.20 m construction height are not interchangeable; the relationship requires careful reading for the proposed geometry.
Mezzanines #
A mezzanine floor is an intermediate floor between two main floors. Its statutory definition requires at least 2.20 m height below it and another 2.20 m between the mezzanine and room ceiling. It must occupy no more than one-third of the carpet area of its containing room and remain open on the side overlooking that room (Regulation 2(84)).
Additional conditions require maintaining the main room's ventilation, limiting overlooking parapets or railings to 1.00 m, and providing suitable light and ventilation before subdividing the mezzanine. No part may be used as a kitchen. The mezzanine must also not exceed one-third of the “entire floor area” (Regulation 13.8(b)). Editor's note: The difference between the definition's “carpet area of the room” and the operational provision's “entire floor area” requires reconciliation for a particular design; neither should silently be substituted for the other.
Annexure VII §5.4 contains different mezzanine height and FAR wording, but is presented for reference and information rather than as an operative exception to Regulation 2(63)(c). See the regulatory clarification below.

Where occupants of a mezzanine exit through the floor below, they must be counted with the lower-floor occupants when calculating exit capacity (Regulation 15.8.1). The capacity of an open mezzanine or balcony is likewise added to the floor below when calculating exit capacity (Regulation 15.8.3). A mezzanine's exclusion from FAR does not remove these fire and life-safety requirements. These clauses were incorporated in the 9 August 2023 amendment (Gazette Series I No. 18, p. 1730 onward). 2023 Gazette source
Attics #
An attic floor or attic storey is the floor immediately above the building's topmost storey, formed under a sloping roof (Regulation 2(15); Chapter 28, Sketch No. 6). The regulations impose two area limits: attic area above any individual room cannot exceed half that room's area, while the combined attic floor area cannot exceed half the building's topmost floor area. Both limits apply (Regulation 13.8(c)). For example, a 20 m² room cannot have more than 10 m² of attic above it, even if the building-wide allowance is greater.
Attics are designated for storage. Where habitation is permitted, the minimum ceiling height is 2.50 m. The access stair must provide at least 0.90 m clear width, and the attic must receive adequate light and ventilation (Regulation 13.8(c)). Sketch No. 6 illustrates an attic habitable room immediately under a sloping roof and labels its floor area as counted for FAR; attic area is not among the Regulation 2(63)(c) mezzanine/loft exclusions. Editor's note: Sketch No. 6 carries a separate 2.10 m annotation, whereas Regulation 13.8(c)(ii) expressly requires 2.50 m minimum ceiling height for permitted attic habitation. The sketch's annotation is not treated as a general relaxation of that textual requirement.


Basements: definition and geometry #
A basement or cellar is a lower storey below the plot's ground level. Under the statutory definition, its floor height is no more than 3.50 m and it projects no more than 1.50 m above surrounding ground (Regulation 2(17)). If it extends beyond the building footprint, the definition prescribes a minimum 1.00 m setback from the plot boundary for areas outside municipal limits. Annexure VI has separate provisions concerning boundary-touching basements and road-level ceilings. These provisions require contextual reconciliation rather than an assumption that every projecting basement may extend to the boundary.
Annexure VI requires a basement floor-to-underside-of-slab height of at least 2.50 m and sets a maximum of 4.50 m (paragraph 2(a)). Paragraph 2(b) permits an increased height, up to 4.50 m, where actually required for specified high-rise or three-/five-star hotel machinery or two-level mechanical car parking; a Fire Services NOC is required. Its ceiling-height provision also places the basement ceiling between 0.90 m and 1.20 m above the average front road level (paragraph 2(d)). Editor's note: Regulation 2(17) defines a basement using a 3.50 m maximum floor height, while Annexure VI states 4.50 m. These figures have different statutory contexts and should not be treated as blanket permission to adopt the higher height without authority-specific clarification.

Permitted basement uses #
The permitted uses of a basement depend on the applicable land-use and zoning controls (Annexure VI, paragraph 1). Specific allowances cover parking, building-service machinery and utilities, bank strong rooms, radiology/X-ray equipment in hospitals with more than 50 beds, and an office-use provision with particular exit and ventilation conditions. Annexure VI paragraph 1(a) simultaneously states a general parking-and-services limitation; paragraph 1(e) allows offices subject to conditions. These provisions must be read together rather than treating office use as unrestricted. Gas-fuelled kitchens are prohibited in basements and sub-basements (Annexure III, paragraph 3.1(k)).
Where basement office use is permissible, Annexure VI paragraph 1(e) limits travel distance to 15.0 m or 7.5 m for a dead end, and requires sufficient exits and access. Non-parking compartments must be between 50 m² and 500 m², with independent ventilation and partitions coordinated with the fire authority. Annexure III paragraph 3.1(e) confines lower basements to car parking alone; the first basement may contain parking, services and other permissible services. Editor's note: The office-use permission must be reconciled with this restriction on lower basements, so it cannot be assumed to apply on every basement level.
Basement access and safety #
For a parking basement, vehicular entry and exit must be conveniently provided from a road at least 10.00 m wide (Annexure VI, paragraphs 1(a) and 2(g)). Access for other permitted uses may be through the main or alternate building staircase; direct road entry is otherwise prohibited. Adequate artificial lighting and ventilation, surface-drainage protection, dewatering pumps on each basement level, watertight walls and floors, and damp-proofing are required (Annexure VI, paragraphs 2(c), (e) and (f)). Mechanical ventilation may address deficiencies; the text gives one exhaust fan per 50.00 m² as an example. Annexure VI paragraph 2(h) discusses basements touching adjacent property subject to indemnity and ground-flush projections; this must be read with Regulation 2(17)'s 1.00 m setback for basement extensions beyond the footprint outside municipal limits. Editor's note: The extent of boundary permission is context-dependent and must not be inferred from the annexure alone.
Fire-safety requirements include at least two independent basement exits sized for actual occupant load, 120-minute fire protection at specified openings to upper occupancies, fire-resistant enclosed stairs with protected lobbies, compartmentation, and independent smoke ventilation for each basement (Annexure III, paragraph 3.1). For parking-only basements the annexure mentions a 45 m travel distance; its ventilation alternatives include perimeter vent area of at least 2.5% of floor area or a specified inlet/outlet system. Annexure III item 3.1 also specifies independent smoke outlets for each basement and compartment, lower-basement mechanical extraction with automatic and manual starting, supply-fan shutoff on fire detection, 12 air changes per hour in fire or distress and alternate power. Ducts are integrated and require fire dampers where they cross the specified electrical areas. Basement openings to upper floors or outside covered by the cutout rule need closely spaced sprinkler heads as a water curtain. Dewatering applies to all basement floors. Closed or open parking structures also refer to NBC 2016 Part 4 Annex H. See Fire Safety and Life Safety. Annexure VI paragraph 2(j), as substituted by the 9 August 2023 Gazette §12, expressly refers each basement floor to Annexure III for fire and safety requirements; former paragraph 2(k) was omitted.
FAR and parking #
Qualifying mezzanine floors and lofts are excluded from the computation of floor area under Regulation 2(63)(c). A room exceeding 5.00 m in height, however, is generally counted twice under Regulation 13.1(b), subject to its exceptions. A basement/cellar qualifies for the specific general FAR exclusion in Regulation 2(63)(a) only when 90% is for vehicle parking and the balance for services or bank safe-deposit vaults. Annexure VI paragraphs 1(c) and (d) separately exclude the specified radiology/X-ray and building-service machinery areas, whereas the office-use area under paragraph 1(e) is counted towards FAR. These are distinct rules, not a general exemption for every allowed basement use. Separately, the 13 August 2026 amendment to Regulation 6A.3 Note (2) applies development charges to mezzanine floors in planning areas, even though Regulation 2(63)(c) excludes them from FAR. Development charges and FAR are different calculations.
A practical example: a 200 m² basement containing 180 m² of vehicle parking and 20 m² of services reaches the stated 90% parking share, but must still satisfy the remaining conditions, permitted-use rules, access, drainage and fire safety. A 200 m² basement with only 160 m² of parking does not meet that particular 90% exclusion test, even if the remainder is a permitted service use. This is a floor-area example, not a certificate of planning approval.
Related subjects and source qualifications #
Additional FAR granted under Regulation 6.1.2 does not change these floor-area exclusions or basement access requirements. Parking must also be available for the additional FAR (Regulation 6.1.2(c)(iii), 24 November 2026 Gazette).
For detailed FAR calculations, see Floor Area Ratio and Floor-Area Calculation. Parking Requirements and Layout covers parking numbers, circulation and the relationship between general and fire-ramp requirements. Rooms, Lighting and Ventilation covers the ordinary room rules.
Regulatory clarification: mezzanine FAR and room height #
The mezzanine definition requires at least 2.20 m clear height both below and above the intermediate floor (Regulation 2(84)). Separately, Regulation 13.1(b) generally counts the floor area of a room more than 5.00 m high twice for FAR purposes, with stated exceptions. These provisions address different questions; neither provision expressly sets a 2.80 m maximum mezzanine floor level.
Annexure VII §5.4 discusses a 2.75 m minimum and counting mezzanine area towards FAR and building height; Annexure VII explicitly describes its material as reference and information only. The operative Regulation 2(63)(c) excludes qualifying mezzanine floors and lofts from floor-area computation. The annexure should not be presented as an equally binding counter-rule or as an automatic override. Regulatory interpretation and approval in a particular project remain subject to competent-authority decisions.
Editor's note on remaining statutory interpretation: The important qualifications remain (1) the operative mezzanine FAR exclusion versus the reference-only Annexure VII paragraph 5.4 discussion; (2) basement height under Regulation 2(17) versus Annexure VI paragraph 2; and (3) Annexure VI's office-use clause versus Annexure III's restriction on lower basements. The controlling authority should resolve any material design-specific uncertainty before a proposed departure is relied upon.
Primary sources: GLDBCR 2010 (September 2024 consolidation), Regulations 2(15), 2(17), 2(63)(a)/(c), 2(81), 2(84), 13.8(a)–(d), 15.8.1, 15.8.3; Annexure III paragraph 3.1; Annexure VI paragraphs 1–2; Annexure VII paragraph 5.4 (reference and information only); Chapter 28 Sketch No. 6. Consolidation: 2024 GLDBCR consolidation. Relevant Gazette amendments: 9 August 2023, §12 (Annexure VI), 2023 Gazette source; 13 August 2026, Regulation 6A.3 Note (2), 2026 Gazette source.
Regulatory notice: This article is an explanatory reference. Check the latest official Gazette and competent authority requirements before making a regulatory decision.