  1. How wide must a stair be?
  2. Corridors and exit doors
  3. When lifts are required
  4. Where accessible facilities apply
  5. Access from arrival to each floor
  6. Toilets, parking and outdoor paths

The clear width of a stair depends on the use and the area or dwellings it serves. Lift requirements depend on vertical travel. Where the accessibility rules apply, the entrance, routes between floors, toilets and parking also have to work as a connected route.

How wide must a stair be? #

A staircase is the part of a building enclosing the stairs and landings for weather protection. It is reserved for the stairs and is not used for habitation. Stair widths are clear of handrails, pardis and other obstructions. [Regulation 2(125) and 13.10(a).]

Occupancy

Dwellings or floor area served

Minimum clear flight width

Residential

Up to 4 dwellings

90 cm

Residential

5 to 8 dwellings

100 cm

Residential

9 to 12 dwellings

115 cm

Residential

13 dwellings or more

120 cm

Commercial

Up to 300 m²

100 cm

Commercial

Over 300 to 600 m²

110 cm

Commercial

Over 600 to 900 m²

125 cm

Commercial

Over 900 to 1,200 m²

140 cm

Commercial

Over 1,200 m²

160 cm

Public utility or institutional

Up to 1,200 m²

150 cm

Public utility or institutional

Over 1,200 to 1,800 m²

180 cm

Public utility or institutional

Over 1,800 m²

200 cm

Source. GLDBCR Regulation 13.10(a), Tables XV–XVII. The middle band of Table XVII is awkwardly printed around 1,200 m². The ranges in the table read the entries in sequence, using the explicit first row at 1,200 m². The text does not expressly reconcile the boundary. Industrial and hazardous buildings follow the NBC provisions referred to in 13.10(a)(iii), which cites the 2005 edition or amendments. Fire egress has its own occupancy and exit-capacity rules under Regulation 15.

The general stair provisions prescribe a riser no higher than 17.5 cm, a tread at least 27 cm, landing depth at least the flight width and 2.2 m clear headroom. Subsidiary service or spiral stairs need at least 70 cm clear width. Shafts, ducts, gas pipes and similar services must stay clear of the staircase. Beams, columns and other features must preserve its headroom and width. Lift doors may not open at a staircase mid-landing.

Above ground floor, a room may be no more than 22.50 m from a staircase. A flight may have at most 14 risers before a landing, except in an individual self-contained unit or single-family dwelling unit. Openings to external air of at least one-tenth of the staircase area are required at each landing except in a single-family dwelling unit. [13.10(b).]

Corridors and exit doors #

Minimum clear corridor or passage width is 0.90 m for residential buildings, 1.20 m for commercial buildings and 1.50 m for public utility or institutional buildings. An exit corridor must also be at least as wide as the aggregate required widths of exit doorways leading in the direction of escape. Corridors through which a staircase discharges need at least 2.40 m headroom. Staircases, lift lobbies and corridors used for exit must be adequately ventilated.

An exit doorway leads to an enclosed stairway or to a horizontal exit through a corridor or passage providing continuous protected egress. The minimum opening is 1.00 m wide or 2.00 m in assembly buildings, and 2.00 m high. Doors swing away from the room and must preserve travel and at least 0.90 m of passage, stair or landing width. The central-corridor note instead directs room doors to open inwards. Sliding and overhead exit doors are excluded. An exit door must open onto a level landing at least as wide as the door, must be openable from the side served without a key, and may not face a flight directly. Mirrors may not be placed in exit routes or on exit doors. [13.10(c).]

When lifts are required #

One lift is required when vertical travel from ground floor exceeds 12 m. At least two are required when vertical travel exceeds 18 m and the area served per floor exceeds 500 m². Lifts, escalators and moving walks follow NBC 2016 Part 8. Lift and fire-lift installation requirements are specifically referred to Section 5 by Annexure III, items 1–2. [13.11(a)–(c).]

Regulation 13.11 generally calls for fire lifts in buildings 15 m high and above. Where applicable, the fire lift is fully automated, carries at least eight passengers and has a ground-level emergency switch and an intercom to the ground-floor control room. Only firefighters operate it during a fire. Population, floor area and compartmentation affect the number and location. Regulation 15 covers the wider fire and egress requirements.

Where accessible facilities apply #

Regulation 16.1 covers buildings and recreational spaces with public access in the listed occupancies: assembly, business/commercial/office/mercantile, educational, industrial, institutional and qualifying residential buildings, plus playgrounds, parks, gardens and beaches. In industry, employee facilities depend on the work. The rule excludes consideration of such arrangements in heavy manufacturing and provides for all disabilities in new light manufacturing factories where persons with disabilities may be employed.

Residential buildings with at least 24 dwellings or at least 2,000 m² built-up area must provide compliant space standards and facilities in at least 20% of the units. Regulation 16.1(vi) refers to the Harmonised Guidelines and Space Standards for Barrier Free Built Environment for Persons with Disability and Elderly Persons.

Editor’s note. Regulation 16.1 introduces the list with a public-access qualification, while the residential entry uses its own size thresholds. The text does not clarify how the qualification is meant to apply to a private residential development that meets those thresholds.

Access from arrival to each floor #

The main entrance has a ramp with railings on both sides. The accessible ramp is at least 120 cm clear, no steeper than 1:12, with a non-slip finish, tactile tiles and bilateral handrails at 80 cm. The slope should be consistent where possible. The adjacent entrance landing is at least 1,800 × 2,000 mm. At the top of a slope the landing uses noticeable colour/brightness or an audible surface cue, with a non-slip wheelchair-traversable finish and level transitions at kerbs. [16.2(1), (3)–(4).]

Each floor needs an accessible lift or a separate accessible ramp. The lift has a door at least 900 mm wide, a car at least 1,500 × 1,500 mm and, where possible, capacity for 13 passengers. It needs Braille markings inside and outside, audio announcements and rails on three sides. Touch screens require an additional physical-button panel with Braille. [16.2(2).]

The accessible entry or exit corridor leading outside to a point offering building-use information is at least 1,500 mm wide. It uses guiding floor finishes or audible guidance. Level changes need a slope no steeper than 1:12, and ramps or sloping ways have handrails on both sides. One stair near the accessible entry or exit must be at least 1,350 mm wide with risers at most 150 mm, 300 mm treads, no abrupt nosing, at most 12 risers per flight and bilateral handrail extensions of 300 mm at each end. [16.2(5)–(6).]

Access and Circulation Within a Plot describes ordinary pathways and driveways. The specific accessible route requirements above still apply where Regulation 16 governs.

Toilets, parking and outdoor paths #

A public building needs one unisex accessible toilet in each toilet block on each floor and an ambulant-accessible cubicle in every block. If a small office building lacks enough floor area for accessible facilities at every floor, one ground-floor unisex accessible toilet can serve it and should adjoin an accessible lift. Subdivided multi-tenant offices require a unisex accessible facility on each floor. Regulation 16.2(7)(c) separately specifies one special WC per floor in a set of toilets, with a washbasin near the entrance.

Feature

Unisex accessible toilet

Special WC

Room

2,200 × 2,000 mm minimum

900 × 2,000 mm minimum

Door

900 mm clear, outward, double-action or sliding with pull bar ≥600 mm

Same

Manoeuvring

1,800 × 1,800 mm clear in front of WC and basin

No equivalent square specified in clause (c)

WC position and transfer

Centre 460–480 mm from side wall. Clear floor 1,350 mm deep × 900 mm wide in front and on transfer side

900 mm width in front and on transfer side

Fittings

Vertical and horizontal rails with ≥50 mm wall clearance. Seat 450–480 mm above floor. At least one basin per floor with 700 mm knee clearance. Emergency opening from outside for any locks.

Same

Source. GLDBCR Regulation 16.2(7)(a)–(c). The two layouts are listed separately and the small-office exception is limited to the specified situation.

Two accessible parking spaces are specified for every 25 car spaces or part of 25. The bay is at least 3.6 m wide, at most 30 m travel from the entrance, reserved and signed. Paths require a smooth, hard and level surface without crossings of vehicular traffic. Avoid grates and manholes. Unavoidable grate bars run perpendicular to travel with gaps at most 12 mm. [16.2(8)–(9).]

Keep projections and obstructions clear to at least 2.1 m above finished floor, avoid recoil doors at public access, and provide prominent simple signs with standard colour and contrast at key locations. Rail and fixture heights must suit children in buildings predominantly used by them. The Harmonised Guidelines, as amended from time to time, govern details not specified in Regulation 16. [16.2(10) and Note.]

Editor’s note. The specific doors allowed in 16.2(7) are toilet-door arrangements. The exit-door restrictions in 13.10(c) apply to doors forming part of an exit route.

Check the current official regulations and applicable standards before making a regulatory decision.