Fire Safety and Life Safety
A-019 · R01 · Awaiting human acceptance
On this page
Fire safety depends on how the building is used, how many people it serves, how they can leave, and whether firefighting vehicles and crews can reach it. These factors also determine when Fire Services clearance is required and which installations the building needs.
Which buildings need Fire Services clearance? #
Occupancy means the principal use of the building or a part, including contingent subsidiary uses. The definitions of building types in GLDBCR 2(20A) and the NBC occupancy group used for fire design serve distinct purposes. A high-rise building under 2(20A)(h) is 15 m or higher, irrespective of occupancy, with height measured under the relevant GLDBCR rules. The Directorate’s Director is the officer defined at 2(33). NBC 2016 includes its amendments under 2(86A). [2(20A), (33), (86A), (93), 15.1.1 and 15.4.]
Regulation 15.2.1 requires the owner or developer to obtain a Directorate of Fire and Emergency Services NOC before applying for the local construction licence and again before applying for occupancy. It applies to any high-rise and to the listed special buildings.
Trigger | Scope |
|---|---|
Height | High-rise buildings. Educational and institutional buildings at least 9 m high. |
Floor area | Hotels, educational, institutional, business, mercantile, industrial, storage, hazardous and mixed occupancies where floor area exceeds 500 m² on any one or more floors. |
Assembly | Assembly buildings. Other buildings with more than 300 m² incidental assembly occupancy on any floor. |
Basements | Two or more basements, or one basement above 500 m². |
Source. GLDBCR 15.2.1. Also obtain a pre-licence NOC for high-rise alterations, modifications or renovation exceeding 500 m² under 15.2.3. Directorate requirements govern records, forms, fees, fire drills and appointment of a fire officer where specified. Regulation 3.6.2(c) also links the construction licence to the Fire Services NOC.
For these buildings 15.1.1 applies NBC 2016 Part 4, except clauses 3.2 and 3.4.4, with the fire provisions in GLDBCR. Firefighting design and installations follow Part 4, and its terms apply unless GLDBCR defines them. For additional FAR or height, 6.1.2(c)(iv) separately requires Fire Services conformity and NOC before applying for the construction licence. The ordinary occupancy clearance still applies where triggered. Structural verification is a separate condition under 6.1.2(c)(ii). [24 November 2026 Gazette.]
High-rise approach and open spaces #
The high-rise approach and open-space rule in 15.1.2 takes precedence over 4.2(g) and 4.4.2 in its scope. The abutting main street is at least 10 m wide. The approach and open spaces on all sides are at least 6 m wide, motorable, hard-surfaced to carry a fire engine up to 45 tonnes, clear of obstructions and projections, and laid out to the Directorate’s satisfaction. Turning radius is at least 9 m.
With no side setbacks or setbacks of 1.5 m or less, provide access through the building on all sides with 5 m clear below the lowest structural member. The main plot entry is at least 6 m wide. The gate folds against the compound wall and a built-over entry has at least 5 m clearance. See Access and Circulation Within a Plot for the ordinary pathway and rear-access rule. [15.1.2(a)–(c).]
How occupant load is established #
The NBC-based groups are A residential, B educational, C institutional, D assembly, E business, F mercantile, G industrial, H storage and J hazardous. NBC Part 4 clauses 3.1.2–3.1.10 supply subgroup details. Mixed occupancies refer to 3.1.1.2 and 3.1.11. Each storey uses the higher of the actual declared number and the Table XXI minimum. Add occupants of a mezzanine discharging to the floor below to that floor, and include an open mezzanine or balcony for exit capacity. The required number of exits cannot decrease in the direction of escape. [15.4 and 15.8.]
Occupancy | Area per person or fixed seating basis |
|---|---|
A Residential | 12.50 m² |
B Educational | 4.00 m² |
C Institutional | 15.00 m² indoor patient, 10.00 m² outdoor patient, 7.50 m² for the dormitories in Note 2 |
D Assembly | 0.65 m² concentrated, 1.40 m² less concentrated without fixed seating, 1.2 × fixed seats, 1.80 m² dining with seats and tables |
E Business | 10.00 m² |
F Mercantile | 3.00 m² street floor and sales basement, 6.00 m² upper sales, 20.00 m² storage or warehouse |
G Industrial / H Storage / J Hazardous | 10.00 / 30.00 / 10.00 m² respectively |
Parking in another occupancy | 30.00 m² |
Source. GLDBCR Table XXI, Notes 1–5. Gross area is measured to inside the external perimeter without deductions for circulation, stairs, shafts, interior walls or other elements. Outside-wall thickness may be included, and factors are gross unless marked net. The dormitory provision covers homes for the aged, orphanages and similar sleeping accommodation. Examples of less concentrated assembly include gymnasia, gaming rooms, libraries and pools. For 300 m² of business space, the table gives 30 people. If 38 are declared, 38 is used.
Assembly and call centres display their limiting occupant load prominently at the entrance to Directorate satisfaction. The preferred engraved metal plate is at least 300 × 200 mm with characters at least 50 mm high and wide and identifies the occupancy, area and limit. [15.8.4 and Sketch 10.]
Exit capacity and travel distance #
Travel distance is the distance to a protected or external escape route or final exit. It is measured from the remotest point of a storey or mezzanine along the natural unobstructed route to the exit door. Exits are as remote as possible from each other and serve direct routes in separate directions. Dead-end corridors are limited to 6 m in educational, institutional and assembly occupancies, 15 m otherwise. [2(142), 15.9.3–15.9.6, Sketch 11.]
Occupancy | Stair width per person | Level component or ramp per person | Travel limit, Types 1–2 / 3–4 |
|---|---|---|---|
A, B | 10 mm | 6.5 mm | 30 m / 22.50 m |
C | 15 mm | 13 mm | 30 m / 22.50 m |
D, E, F | 10 mm | 6.5 mm | 30 m / 30 m |
G industrial | 10 mm | 6.5 mm | G-1/G-2 45 m, G-3 22.50 m / prohibited |
H storage | 10 mm | 6.5 mm | 30 m / prohibited |
J hazardous | 18 mm | 10 mm | 22.50 m / prohibited |
Source. GLDBCR Tables XXII–XXIII. Fully sprinklered buildings may increase listed travel distances by 50%. Parking ramps below the first basement do not count as exits. Stair and door capacity uses 500 mm units and an additional half-unit for 250 mm, ignoring smaller remainders. Doors, stairs, level components and ramps must serve the floor’s load without losing capacity along the way. The smallest component limits the route. A 1,000 mm doorway at 6.5 mm/person gives about 153 people, shown conservatively as 150 in the note. A stair serving that doorway at 150-person capacity limits the complete route to 150. Determine number and width together with travel distances and occupancy-specific minimums. [15.9.3–15.9.6.]
Protected routes and exit doors #
Every human-occupancy building needs sufficient exits under 15.9.1 and NBC Part 4 clauses 4.2–4.4.2.5. Regulation 15.9.2(d) states a minimum-exit-requirement exception for buildings or structures not accessible for general public use. It appears alongside the adequate-escape rule for all human occupancy. The two provisions must be assessed together. Exit paths, passageways and discharge remain unobstructed, and alterations preserve required number, width and protection. Access should avoid passing through other occupied units or corridors in others’ control where that restricts egress. Lifts, escalators, moving walks and revolving doors generally do not count, subject to the specific revolving-door rule. Non-naturally ventilated areas need 120-minute fire doors, particularly at lift lobbies and stair wells. At least half of required upper-floor exit stairs, rounded up, discharge directly outside or via exit passageways. Unless specifically varied, clear height is at least 2.4 m on exit routes and 2 m at exit doors. [15.9.2.]
Level changes above 300 mm require ramps or sloped surfaces with handrails and contrasting finishes. Exit access walking surfaces are nominally level and slip-resistant, with slope at most 1:20 along travel unless ramp provisions are met and cross slope at most 1:48. Protected exits are penetrated only for necessary services such as fire protection or pressurisation and with passive protection. Access restrictions, including turnstiles and barriers, must clear automatically in emergencies. Where installed, provide alternative exit width within 3 m of turnstiles. [15.9.2(k)–(q).]
Exit doorways are at least 1,000 mm wide and 2,000 mm high, with 2,000 mm width for assembly, into an enclosed stair or protected horizontal route. Bathroom and WC doors are at least 750 mm, with the referenced accessibility requirements for accessible toilets and the greater of 1,000 mm and the referenced accessibility width for other applicable doors. Doors open in egress direction without keys and no overhead or sliding exit doors or mirrors are allowed. Assembly and C-1 hospital or sanatorium doors open via a landing so they do not impede descending traffic. Other occupancy doors may not reduce the landing path by more than half of stair width. Central-corridor room doors open inwards except assembly rooms. Exit routes also need enough corridor width for the aggregate exit-door width. [15.9.2(h), 15.9.7, 15.9.8, Sketches 8A–9 and 12–13.]
A revolving door is accepted only with book-fold parallel paths at least 1,000 mm wide, at least 3 m from stairs or escalators with dispersal area, and a same-capacity hinged door in the same wall within 3 m. It counts for 50 people only. Folding-partition doors are excluded. Fire-door assemblies need certified hardware and identifying and rating labels. Access-controlled doors must have the applicable rating, unlock on activation of fire detection or sprinklers until manual reset, unlock on relevant power loss and have a readily accessible, signed independent push-to-exit release. [15.9.7(e)–(i).]
Fire stairs and ramps #
Buildings specified in 15.2.1 have at least two staircases, with actual number under 15.9.3 and NBC Part 4 occupancy provisions. At least half discharge directly or via exit passageways. Others can discharge through a large lobby. Fire stairs have a maximum riser of 150 mm and 12 risers per flight. Treads excluding nosing are non-slip and at least 250 mm for residential or 300 mm for assembly, hotels, educational, institutional, business and other buildings. Only compliant enclosed stairs qualify as described by 15.9.9(I). Stairs, Lifts and Accessibility covers the ordinary stair rules of Regulation 13.10. [15.9.9(I).]
Minimum internal widths are 1.00 m for A-2, 1.25 m for A-1/A-3/A-4, 1.50 m for A-5/A-6 hotels and educational, 2.00 m for assembly and institutional, and 1.50 m for others. Assembly below 150 occupants may be accepted at 1.50 m. Handrails are on one side below 1,500 mm and both sides at or above that. The text mentions both 115 mm projection and 90 mm into measured width. Editor’s note. The two clauses use different language for the projection into a staircase and into its measured width. The larger projection limit does not displace the stated measured-width limit. [15.9.9(II)(e)–(g).]
Internal stairs are non-combustible and 120-minute rated, with at least 2.2 m under stair and landing, 120-minute doors and any permitted openings. They cannot wrap a lift shaft, act as adjoining air ducts or admit lifts, living spaces, stores, fire risks, pipes, shafts or mechanical and electrical equipment. Width and headroom remain clear of structural or decorative encroachment. Pressurisation or natural or cross ventilation follows NBC Part 4 clause 4.4.2.5 Table 6. Above 30 m provide cross ventilation as specified or pressurisation. Keep routes continuous from applicable refuge or terrace levels to discharge, mark floors inside and outside the stair, and provide the 300 × 200 mm minimum indicator board near the fire door. Basement access uses a separate staircase unless separated by a fire protection wall with separate entries. Scissor stairs do not count. [15.9.9(II), Sketch 14.]
Curved stairs can be exit access only with at least 280 mm tread at 350 mm from the narrow end and a smallest radius at least twice stair width. Spiral stairs are limited to low occupant loads and buildings up to 9 m, with at least 1,500 mm diameter and adequate headroom. External stairs are usable, directly ground-connected, remote from internal stairs, non-combustible and protected from openings within 3 m by 60-minute assemblies. They need 120-minute access doors and 120-minute external openings of at least one-tenth stair area at each landing. Use straight flights at least 1,500 mm wide and at most 45°, with both handrails 1,000–1,200 mm high and baluster gaps at most 150 mm. [15.9.9(III)–(V).]
Egress ramps follow NBC Part 4 clause 6 and applicable stair enclosure, capacity and dimension rules. The maximum slope is 1:12, printed with ‘8 percent’ in brackets. Use approved slip-resistant unperforated surfacing, no width decrease and landings at each end and door. Direction changes need 1.5 × 1.5 m landings. Landing length is normally 1.5 m, or 1.25 m in the straight non-accessible case. Provide bilateral handrails and avoid outdoor ponding. The pedestrian provisions do not apply to basement car-parking ramps. The vehicular rule is at least two ramps, preferably at opposite ends, each at least 3.60 m wide and no steeper than 1:8. See Mezzanines, Lofts, Attics and Basements for additional basement requirements. [15.9.10 and Annexure III.]
Fire-rated construction and installed systems #
A fire-resisting wall is rated with protected openings and continuous construction from the foundation to at least one metre below the roof as the definition in 2(60) specifies. Fire-resistant materials use the relevant NBC 2016 and BIS ratings under 2(66). Structural and non-structural fire resistance follows NBC Part 4 clause 3.3 to Directorate satisfaction. Glazing follows NBC Part 6 Section 8, with the assembly rated to construction type under Part 4 clause 3.4.1 Table I. Glass is barred in exit and exit-passage enclosures. Glass façades follow Part 4 clause 3.4.10.2. [15.5–15.7.]
Fixed firefighting installations under 2(61) are non-passive installations incorporated for audiovisual and suppression measures for combating fires. Select them by occupancy and height under NBC Part 4 clause 5. Lightning protection, compartmentation, smoke control and additional use-specific provisions refer to clauses 3.4.6.5, 4.5, 4.6 and 6. Basement and service fire requirements refer to Annexure III. Items 5–13 refer to NBC Part 4 provisions on ducts and refuse chutes, electrical services, stair and corridor lighting, air-conditioning, fire dampers, boiler rooms, alternate supply, substations and fire command centres. Item 4 also specifies a terrace helipad above 200 m, with airport approval and structural safety from an IIT or NIT. This requirement does not confer permission to build to that height. Lightning protection is to the Electricity Department’s satisfaction for 15.2.1 buildings, buildings with ground or stilt plus at least two floors, or height of at least 9 m from adjacent ground. [15.10–15.11.]
Annexures VII and VIII reproduce NBC 2005 general and occupancy guidance for reference. Their older occupant-load table and special occupancy examples are informational. The operative fire provisions are Regulation 15 and the provisions of NBC 2016 Part 4 that it applies.
Check the current official regulations and applicable standards before making a regulatory decision.